***Note: Many local criminal codes can now be located under Chapter 10.60 SMC while others are now cited under the Revised Code of Washington (RCW), which was incorporated into the municipal code in 2022. (See SMC 10.58.010). Code Enforcement, including Noise Control and Animal Regulations are located in Chapters 10.62 through 10.74.

Home
Title 17F
Chapter 17F.030
Section 17F.030.060
 

Title 17F Construction Standards

Chapter 17F.030 Boiler and Pressure Vessel Code

Section 17F.030.060 Installation Clearance – Front, Back and Sides

When boilers are replaced or new boilers installed in either existing or new buildings, sufficient access must be provided for inspection, maintenance, operation and repair. As a minimum clearances at sides, front and back wall shall be the manufacturer’s recommendations, but in no case less than eighteen inches. Boilers having manholes shall have five feet clearance from the manhole opening and any wall, ceiling or piping that will prevent a person from entering the boiler (Reference WAC 296-104-256).

Date Passed: Monday, August 14, 2006

Effective Date: Wednesday, September 27, 2006