***Note: Many local criminal codes can now be located under Chapter 10.60 SMC while others are now cited under the Revised Code of Washington (RCW), which was incorporated into the municipal code in 2022. (See SMC 10.58.010). Code Enforcement, including Noise Control and Animal Regulations are located in Chapters 10.62 through 10.74.

Home
Title 17F
Chapter 17F.030
Section 17F.030.080
 

Title 17F Construction Standards

Chapter 17F.030 Boiler and Pressure Vessel Code

Section 17F.030.080 Installation – Clearance at Top of Boilers

When boilers are replaced or new boilers installed in either existing or new buildings, a minimum clearance as specified below must be provided between the top of the boiler proper and ceiling.

  1. For power boilers having a steam-generating capacity in excess of five thousand pounds per hour, or a heating surface in excess of one thousand square feet, or input in excess of five million BTU per hour, the clearance is seven feet.
  2. For:

    1. low-pressure heating boilers which exceed any one of the following limits:

      1. five million BTU input,

      2. five thousand pounds steam per hour capacity or one thousand square feet heating surface, and

    2. power boilers which do not exceed any of the following limits:

      1. five million BTU input,

      2. five thousand pounds steam per hour capacity or one thousand square feet heating surface, and

    3. all boilers with manholes on top of the boiler, except those described in subsection (A) of this section, the clearance is three feet.
       
  3. For low-pressure heating boilers which do not exceed the above limits and miniature boilers, the clearance is two feet.

Date Passed: Monday, February 28, 2005

Effective Date: Saturday, April 2, 2005

ORD C33594 Section 2