Title 13 Public Utilities and Services
Chapter 13.04 Water
Article I. General Provisions
Section 13.04.080 Construction Specific
ati ons
Construction shall meet City of Spokane Water and Hydroelectric Services Department Rules and Regulati ons for Water Service Installati ons.
Every service pipe shall be provided with a ball valve for each recipient, easily accessible, placed inside the foundati on wall, beyond damage from frost, and so situated that the water can be conveniently shut off and drained from the pipes.
All water pipes in buildings shall be so arranged as to drain toward the drain cocks placed for that purpose.
All water pipe shall be soft annealed Type K copper water pipe or approved equal as provided in the director's regulati ons. Use of HDPE is outlined in the City of Spokane Water Department Rules and Regulati ons for Water Service Installati ons.
All service pipes inside property lines shall hereafter be laid to a depth of at least five feet below the surface of the ground.
All service pipes laid inside the property line on any premises shall be left exposed in the trench until inspected by the water service inspector, and when they have passed inspection and have been approved, the pipes shall be properly covered by the property owner.
Date Passed: Monday, December 8, 2025
Effective Date: Sunday, January 18, 2026
ORD C36777 Section 12