International Fire Code chapter 33, Fire Safety During Construction and Demolition, requires approval of safety precautions during construction. These precautions shall include the following for mixed-use residential buildings being constructed in accordance with the provisions of this title:

  1. To minimize the size of fire and control radiant heat that could threaten buildings in close proximity:

    1. assure that apparatus set-up areas are available to direct master streams on exposures in the event of a fire. Access to all exterior exposures shall not exceed one hundred fifty feet from the fire truck setup locations;

    2. activate sprinklers as soon as practical. 

  2. To control fire spread to other buildings, horizontal openings within twenty feet of other buildings will be provided with a minimum of three-quarter-inch plywood; these openings may remain open during work hours, but are required to be closed after hours. Care shall be taken to use appropriate materials and/or weather protection considering the stage of exposure to the weather.