City of Spokane

Spokane Municipal Code

Home
Title 17F
Chapter 17F.080
Section 17F.080.010
 

Title 17F Construction Standards

Chapter 17F.080 Fire Code

Section 17F.080.010 Adoption of International Fire Code
  1. The Washington State current amended edition of the International Fire Code (IFC) and related standards, published by the International Code Council, as modified by this title, is the fire code of the City of Spokane except as otherwise provided.
  1. The following amendments are made to the International Fire Code:
  1. Section 101.1 is modified to read as follows:
    1. Title.

These regulations shall be known as the fire code of the City of Spokane, hereinafter referred to as “this code.”

  1. Section 109.4 is modified to read as follows:
    1. Violation Penalties.

Persons who shall violate a provision of this code or shall fail to comply with any of the requirements, thereof, or who shall erect, install, alter, repair, or do work in violation of the approved construction documents or directive of the fire code official or of a permit or certificate used under provisions of this code shall be subject to the provisions of chapter 1.05 SMC.

  1. Section 112.4 is modified to read as follows:
    1. Failure to Comply.

Any person who shall continue any work after having been served with a stop work order, except such work as that person is directed to perform to remove a violation or unsafe condition, shall be subject to penalties identified in chapter 1.05 SMC.

  1. IFC Sections 503.1.2, 503.1.3, 503.2, 503.3, and 503.4 are adopted as published. Section 503.1.1 is adopted and revised as follows:

503.1.1 Buildings and facilities. Approved fire apparatus access roads shall be provided for every facility, building or portion of a building hereafter constructed or moved into or within the jurisdiction. The fire apparatus access road shall comply with the requirements of this section and shall extend to within 200 feet (60 960 mm) of all portions of the facility and all portions of the exterior walls of the first story of the building as measured by an approved route around the exterior of the building or facility.

Exceptions:

  1. For buildings equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3 the distance shall extend to 240 feet.
  1. Fire apparatus access roads cannot be installed because of location on property, topography, waterways, nonnegotiable grades or other similar conditions, and an approved alternative means of fire protection is provided.
  1. There are not more than two Group R-3, IRC, or Group U occupancies.
  1. Where approved by the fire code official, fire apparatus access roads shall be permitted to be exempted or modified for solar photovoltaic power generation facilities.
  1. Chapter 56 is amended with chapter 10.33A SMC.
  1. Section 903.2.11.5 is revised to read:
      1. A wet chemical suppression system shall be installed in a commercial kitchen exhaust hood and duct system to meet the compliance of Section 904.
  1. Section 904.2.2 is revised to read:
      1. Each required commercial kitchen exhaust hood and duct system required by Section 609 to have a Type 1 hood shall be protected with a wet chemical suppression system installed in accordance with this code.
  1. Section 904.12.

Replace the first paragraph and the five types to read: 

    1. 904.12 – Commercial Cooking Systems.

The automatic fire extinguishing system for commercial cooking systems shall be a wet-chemical type system. The wet-chemical system shall be tested in accordance with UL 300 and listed and labeled for the intended application. The system shall be installed in accordance with this code, its listing, and the manufacturer’s installation instructions. Wet-chemical extinguishing systems shall be installed in accordance with NFPA 17A.

  1. Section 904.12 – Exception; Section 904.12 Items 1, 2, 3, 4, and 5; Section 904.12.3; Section 904. 12.4 are not adopted.
  1. Section 905.1 – Add the following to end of the paragraph:

Class II and Class III standpipes are not allowed for new standpipes in the City of Spokane. All requirements for Class II and Class III shall be Class I and references to one- and one-half inch outlets shall be changed to two and one-half inches. There are no requirements for two and one-half inch hose to be provided (i.e., stages).

  1. Section 906.1.

Add exception to read as follows:

    1. Portable fire extinguishers are not required for residential buildings that do not have an interior or exterior common space.
  1. Section 1011.14.

Remove “and for access to unoccupied roofs” from last sentence.

  1. Section 1011.12

Remove “alternating tread device,” from exception.

  1. Section 1023.9.

Revise the second sentence to read as follows:

“. . . the story of, the number of floors above grade (if it is different from the story number), and the direction . . .”

  1. Section 5704.2.9.6.1 Modify to read:

“outside of buildings shall be in accordance with table 5705.3.4(2)

  1. Section 5706.2.4.4 Modify to read:

Remove the last part of the last sentence: outside of buildings shall be in accordance with table 5705.3.4(2)

  1. Section 5806.2 Modify:

Remove the last part of the last sentence: outside of buildings shall be in accordance with the requirements of the Authority Having Jurisdiction

  1. Section 6104.2.

Remove the last part of the last sentence: “(Jurisdiction to specify)”.

Date Passed: Monday, October 11, 2021

Effective Date: Monday, October 11, 2021

ORD C36115

May 3, 2024